자동로그인
 

현재위치 : Home > DAVIS (상품 25000개) > 전기계측기 Electrical > 전력분석기

 
LM300 Graphical Power Quality Instrument
    · 고객선호도 :
    · 시중가격 :
    · 판매가격 :
    · 포 인 트 :
    · 수 량 :


회원이 되시면 가격변동정보, 신제품, 특판제품, 기술정보등 다양한
뉴스정보를 보내드립니다.
배송은 평균 2~3일정도 예상됩니다.
                    (0)                     (0)                     (0)

Analyst 3Q – 3 Phase, 7 Channel Hand Held Graphical Power Quality Measurement

The Power Quality Analyzer combines the functionality of power quality meter, disturbance analyser, and data logger in a single hand held instrument which has been designed for safety and ease of use. This is the ideal troubleshooting tool to identify and quantify power quality problems that effect the performance and efficiency of electrical plant and equipment.


The Power Quality industries’ leading software

Allows the viewer to scroll through event, timeline and waveform data simultaneously, zero in on captured disturbance waveforms, scan historical trends, evaluate static’s and perform harmonic and interharmonic analysis-all with the click of a mouse. With it’s intuitive two-pane browser, complete report writing capabilities, Windows® interface and simple-to-use visualization and analytical capabilities, this software turns every user into a power quality expert.
 
Features
  • 3 Phase power quality meter, oscilloscope and data logger in one instrument ideal for trouble shooting, load profiling and supply monitoring
  • Numerical display of RMS values of current and voltage, plus frequency, power, energy, flicker and related parameters
  • High resolution backlit display (320 x 240) for waveform, harmonics, chart and multi parameter display
  • Unique graphical overview mode for all key power quality parameters on one screen for fast identification of power quality problems, including harmonics, flicker, imbalance, interruptions, dips and frequency
  • Assessment of voltage quality parameters according to EN50160 in single or three phase systems, star or delta configuration
  • Internal trend recording with real time clock for RMS values of voltage and current, power, energy, harmonics and flicker to identify intermittent problems
  • Automatic recording of Min-, Max-, average values (1/2 cycle values) and simple detection and measurement of dips, surges and interruptions
  • Unique vector diagram for analysis of imbalance of the three phase voltages and currents
 
 
SPECIFICATIONS
Built-in 1.5 MB memory for data logging, saving screens and capturing of up to 100 events with adjustable thresholds
 On screen analysis or data download via RS232 for reporting and archiving of results
 Four channel (incl. neutral) current measurement with Flex current probes or conventional CT's up to 3000A
 NiMH rechargeable battery giving 24 hours operation or mains powered for continuous use
Safety IEC 61010-1, 600V CATIII, Pollution degree 2

SPECIFICATIONS
Nominal Voltage Delta: 200/400/830V
Star: 115/230/480V
Intrinsic Error 115V - 830V – 0.2%; Resolution 0.1V
Current Ranges 30/300/3000A; Intrinsic Error 0.5% (excludes probe); Resolution 0.01A
Power Intrinsic Error 1%; Resolution 1W
Frequency Range 45-65Hz; Intrinsic Error 0.2%; Resolution 0.01Hz
Harmonics 1st-40th Vrms, Irms, THD V, THD I
Imbalance Intrinsic Error 0.5% resolution 1deg;
Events Intrinsic Error 1%; Flicker FL, Pst, Plt, IEC 1000-4-15; Intrinsic Error 3%
Catalog No. Description Price
Model LM300 Description: Graphical Power Quality Instrument. 7-channel (4) 30/300/3000A flex CTs, 3 voltage leads, re-charger, Software and hard case 9,170,820
번호 제목 작성자 작성일 평가점수
이 상품에 대한 사용후기가 아직 없습니다.
사용후기를 작성해 주시면 다른 분들께 많은 도움이 됩니다.
 
* 이 상품을 사용해 보셨다면 사용후기를 써 주십시오.
번호 제목 작성자 작성일 답변
이 상품에 대한 질문이 아직 없습니다.
궁금하신 사항은 이곳에 질문하여 주십시오.
 
* 이 상품에 대한 궁금한 사항이 있으신 분은 질문해 주십시오.
이 상품과 관련된 상품이 없습니다.
 
회사소개 | 서비스이용약관 | 개인정보취급방침
주소 : 경기도 성남시 중원구 둔촌대로 474, 708호 (상대원동 선텍시티1)
Tel : 031-777-1588 / Fax : 031-777-1587 / 개인정보관리책임자 : 관리자
사업자 등록번호 : 116-81-31753 / 통신판매업신고 : 2005-경기성남-0886호
대표자 : 홍영화 / 운영자 : 윤상미
상호 : 주식회사 코린스 / Copyright ⓒ 2002. All Rights Reserved.
가입사실확인